General explosion-proof performance test items for explosion-proof electrical equipment
project |
Basis and requirements |
Appearance inspection |
Manufacturing drawings and enterprise standards (technical conditions) |
Dimensions and weight |
Installation and connection dimensions |
Electrical clearance and creepage distance |
GB3836.3-4.3、 4.4 Phase to phase and shell connection after wiring, Table 4 of GB3836.4 |
Interlocking devices, warning signs |
GB3836.1-10 Special Tool Interlocking Device |
a fastening |
GB3836.1-9 Anti loosening, perforation exposure, blind hole retention |
Coatings and paints |
Corrosion and arc resistance |
Internal and external grounding |
GB3836.1-15 Symbols, Materials, and Dimensions |
connection |
Reliable connection, neat arrangement, and distinct colors |
Mechanical testing |
GB3836.1-23.4.3 Impact and Drop (Some Products and Parts) |
Shell protection performance test |
GB3836.1-23.4.4 (Explosion proof type not tested) |
Twist test of connectors |
GB3836.1-23.4.5 (Torque Action) |
Temperature test |
GB3836.1-23.4.6 Surface Temperature, Thermal Stability of Plastic Shells, Transparent Components of Luminaires |
Measurement of Insulation Resistance of Plastic Shell |
Thermal upheaval |
Reference device clamping test |
GB3836.1-7.3.1 |
Damp heat test |
GB3836.1 Appendix D Clamping Effect and Mechanical Strength |
Rubber component aging test |
GB3836.1 Appendix C Alternating Damp Heat Test GB3836.1 Appendix D: The change in Shore hardness after aging shall not exceed 20% |
Note: The general test items listed in this table are applicable to explosion-proof, increased safety, intrinsic safety, and general mining electrical equipment. There may be differences according to the actual situation of the product.
Service Hotline: 18924609560 (same WeChat account)
![]() |
||||||
![]() |
||||||
|
||||||
![]() |
||||||
|
||||||
![]() |